Safety Recommendation M-98-125
Details
Synopsis: ON 7/20/98, A FIRE OCCURRED ON BOARD THE LIBERIAN-REGISTERED PASSENGER VESSEL ECSTASY, OPERATED BY CARNIVAL CRUISE LINES. THE VESSEL HAD JUST DEPART PORT OF MAIMI, FLORIDA, BOUND FOR KEY WEST, FLORIDA, WITH 2,557 PASSENGERS & 920 CREWMEMBERS ABOARD. AT 1710, THE SHIP'S FIRE ALARM SYSTEM ON THE BRIDGE SOUNDED, INDICATING THAT A MANUAL ALARM HAD BEEN ACTIVATED IN THE LAUNDRY ROOM. FIRE SPREAD THROUGH THE LAUNDRY VENTILATION SYSTEM, & FLAMES & LARGE VOLUMES OF SMOKE WERE SEEN ISSUING FROM THE STERN OF THE VESSEL. THE VESSEL LOST PROPULSION & STEERING AS A RESULT OF THE FIRE, WHICH WAS BROUGHT UNDER CONTROL & EXTINGUISHED ABOUT 2109. THE SHIP WAS RETURNED TO ITS BERTH AT PORT OF MIAMI AT 0220 ON JULY. ALL PASSENGERS SAFELY DISEMBARKED BEFORE 0600. NO FATALITIES OCCURRED; THE INJURED INCLUDED 14 CREWMEMBERS & 6 PASSENGERS.
Recommendation: THE NTSB RECOMMENDS THAT THE (CRUISE VESSEL OWNER & OPERATOR): IMMEDIATELY INSPECT, WITHIN YOUR FLEET OF SHIPS THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, & EXHAUT TERMINEUSES, FOR ANY COMBUSTIBLE MATERIALS, SUCH AS LINT, & CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE. (URGENT)
Original recommendation transmittal letter: PDF
Overall Status: Closed - Acceptable Action
Mode: Marine
Location: Harbor, United States
Is Reiterated: No
Is Hazmat: No
Is NPRM: No
Accident #: DCA98MM035
Accident Reports:
Fire On Board Liberian Passenger Ship Ecstasy
Report #: MAR-01-01
Accident Date: 7/20/1998
Issue Date: 10/20/1998
Date Closed: 3/17/2000
Addressee(s) and Addressee Status: American Hawaii Cruises and Delta Queen Steamboat Company (Closed - Acceptable Action)
Bergen Line, Inc. (Closed - Unacceptable Action - No Response Received)
Celebrity Cruises, Inc. (Closed - Acceptable Action)
Commodore Cruise Line (Closed - Acceptable Action)
Costa Cruise Lines (Closed - Acceptable Action)
Crystal Cruises (Closed - Acceptable Action)
Cunard Line Ltd. (Closed - Acceptable Action)
Disney Cruise Line (Closed - Acceptable Action)
First European Cruises (Closed - Acceptable Action)
Holland America Line, Inc. (Closed - Acceptable Action)
Mediterranean Shipping Company (Closed - Acceptable Action)
Norwegian Cruise Line (Closed - Acceptable Action)
Norwegian Cruise Line, Orient Lines (Closed - Acceptable Action)
Premier Cruise Lines (Closed - Acceptable Action)
Princess Cruise Lines (Closed - Acceptable Action)
Radisson Seven Seas Cruises (Closed - Acceptable Action)
Renaissance Cruises, Inc. (Closed - Acceptable Action)
Royal Caribbean Cruises Ltd. (Closed - Acceptable Action)
Royal Olympic Cruises (Closed - Acceptable Action)
Silversea Cruises Ltd. (Closed - Acceptable Action)
Keyword(s):

Safety Recommendation History
From: NTSB
To: Norwegian Cruise Line, Orient Lines
Date: 3/15/1999
Response: THE BOARD IS PLEASED TO LEARN THAT ORIENT LINES, INC. HAS HAD A GENERAL DUCT-CLEANING PROGRAM IN PLACE FOR ITS VESSEL UTILIZING ULTRA-SOUND, VACUUM, AND SANITIZING EQUIPMENT. IN ADDITION, THE BOARD IS PLEASED THAT ORIENT LINES, INC. HAS INSTIGATED A PRIORITY CONCENTRATION ON INSPECTING AND CLEANING LAUNDRY VENTILATION SYSTEMS AND THAT PROGRAM WILL CONTINUE TO BE PERFORMED ON AN ON-GOING BASIS. BECAUSE THE INSPECTIONS AND CLEANINGS WILL CONTINUE AS REQUESTED, M-98-125 AND -126 HAVE BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Norwegian Cruise Line, Orient Lines
To: NTSB
Date: 11/18/1998
Response: Letter Mail Controlled 11/24/98 1:34:21 PM MC# 981396 WE WOULD LIKE TO THANK YOU FOR SENDING US A COPY OF THE NTSB RECOMMENDATIONS REFERENCED ABOVE. WE WOULD LIKE TO INFORM YOU THAT ORIENT LINES ALREADY HAD A GENERAL DUCT-CLEANING PROGRAM IN PLACE FOR OUR VESSEL UTILIZING ULTRA-SOUND, VACUUM, AND SANITIZING EQUIPMENT. HOWEVER, IN LIGHT OF NTSB'S RECOMMENDATIONS, WE HAVE INSTIGATED A PRIORITY CONCENTRATION ON INSPECTING AND CLEANING OF LAUNDRY VENTILATION SYSTEMS. SUCH INSPECTION AND CLEANING WILL CONTINUE TO BE PERFORMED ON AN ON-GOING BASIS IN ACCORDANCE WITH M-98-125 AND -126.

From: NTSB
To: Commodore Cruise Line
Date: 2/19/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT THE LAUNDRY VENTILATION SYSTEMS OF COMMODORE CRUISE LINES' VESSELS ENCHANTED ISLE AND UNIVERSE EXPLORER WERE INSPECTED SUBSEQUENT TO THE FIRE ON BOARD CARNIVAL'S ECSTASY AND THAT EACH VESSEL HAS RECEIVED PERIODIC INSPECTIONS AND MAINTENANCE OF ITS MAIN LAUNDRY VENTILATION SYSTEMS SINCE THE VESSELS WERE PLACED UNDER V. SHIPS MARINE, LTD.'S MANAGEMENT. THE BOARD FURTHER UNDERSTANDS THAT INSPECTION AND MAINTENANCE HAVE BEEN INCORPORATED INTO THE VESSELS' PLANNED MAINTENANCE SYSTEM AND THAT V. SHIPS MARINE, LTD. FORWARDED COPIES OF OUR 10/20/98, LETTER TO BOTH VESSELS TO REINFORCE THE CRITICAL NATURE OF THIS MAINTENANCE IN REGARD TO FIRE SAFETY. ACCORDINGLY, M-98-125 AND -126 HAVE BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Commodore Cruise Line
To: NTSB
Date: 12/22/1998
Response: Letter Mail Controlled 12/29/98 1:41:22 PM MC# 981509 V. SHIPS MARINE, LTD. (VSML) ARE MANAGERS OF THE PASSENGER VESSELS, ENCHANTED ISLE AND UNIVERSE EXPLORER, ON BEHALF OF COMMODORE CRUISE LINE. COMMODORE CRUISE LINE'S PRESIDENT, MR. JAMES SULLIVAN, FORWARDED A COPY OF YOUR 10/20/98 LETTER, CONTAINING THE ABOVE REFERENCED RECOMMENDATIONS, TO OUR ATTENTION FOR REVIEW AND RESPONSE. COMMODORE'S VESSELS HAVE RECEIVED PERIODIC INSPECTIONS AND MAINTENANCE OF THEIR MAIN LAUNDRY VENTILATION SYSTEMS SINCE THEY WERE PLACED UNDER OUR MANAGEMENT. THIS INSPECTION AND MAINTENANCE WAS SUBSEQUENTLY INCORPORATED INTO THE VESSELS' PLANNED MAINTENANCE SYSTEM. WE FORWARDED COPIES OF YOUR LETTER TO BOTH VESSELS TO REINFORCE THE CRITICAL NATURE OF THIS MAINTENANCE IN REGARDS TO FIRE SAFETY. THE LAUNDRY VENTILATION SYSTEMS ON BOTH VESSELS WERE INSPECTED SUBSEQUENT TO THE FIRE ON BOARD CARNIVAL'S ECSTASY. IN VIEW OF THE FOREGOING, WE BELIEVE BOTH VESSELS ARE IN FULL COMPLIANCE WITH NTSB RECOMMENDATIONS M-98-125 AND -126. PLEASE FEEL FREE TO CONTACT US IF YOU REQUIRE ANY FURTHER INFORMATION.

From: NTSB
To: Princess Cruise Lines
Date: 3/12/1999
Response: THE SAFETY BOARD STAFF CONTACTED CAPTAIN DAVID BROWN OF YOUR STAFF TO CLARIFY THE ACTION YOU HAVE TAKEN ON THESE RECOMMENDATIONS AND FOR FURTHER INFORMATION ON THE CLEANING AND MAINTENANCE PROGRAM AT PRINCESS. MY STAFF LEARNED THAT PRINCESS HAS HAD A MAINTENANCE MANAGEMENT SYSTEM (MMS) IN PLACE FOR QUITE SOME TIME, AND THAT THE THOROUGH INSPECTION OF THE LAUNDRY ROOM VENT SYSTEM IS PART OF THE MMS PROGRAM. WE NOW UNDERSTAND THAT ALL NINE VESSELS HAVE BEEN INSPECTED IN ACCORDANCE WITH THE COMPANY MMS PROGRAM, WHICH INCORPORATED A THOROUGH INSPECTION OF THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS AND EXHAUST TERMINUSES. WE FURTHER UNDERSTAND THAT PRINCESS HAS CLEANED THE DUCTS ON ALL OF ITS VESSELS, AS NEEDED, TO REDUCE THE RISK OF FIRE. IN ADDITION, OUR INFORMATION INDICATES THAT THE MMS PROGRAM INCLUDES A DAILY CHECKS BY SHIPBOARD PERSONNEL OF THE FILTERS AND VENT SYSTEM IN THE VESSEL LAUNDRY ROOMS TO ENSURE THAT THE SYSTEM IS CLEAN AND CLEAR OF ANY COMBUSTIBLE MATERIAL THAT COULD POSE A FIRE HAZARD. BECAUSE PRINCESS HAS AN ONGOING LAUNDRY VENTILATION SYSTEM INSPECTION AND CLEANING PROGRAM, M-98-125 AND -126 HAVE BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Princess Cruise Lines
To: NTSB
Date: 11/5/1998
Response: WE ALREADY HAVE A PROGRAM IN PLACE FOR THE INSPECTION OF LAUNDRY VENTILATION SYSTEMS WHICH IS CARRIED OUT ON WEEKLY/MONTHLY BASIS, DEPENDING ON THE AREA. THEY ARE CLEANED ON A THREE MONTHLY BASIS. PRINCESS PROVIDED A LIST OF THE LAST DATES FOR THE CLEANING OF SEVERAL OF ITS VESSELS.

From: NTSB
To: Silversea Cruises Ltd.
Date: 7/8/1999
Response: M-98-125 ASKED THAT SILVERSEA CRUISES LTD. (SILVERSEA) IMMEDIATELY INSPECT, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE. BECAUSE SILVERSEA IMMEDIATELY INSPECTED, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEANED THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Silversea Cruises Ltd.
To: NTSB
Date: 4/5/1999
Response: Letter Mail Controlled 4/6/99 3:31:57 PM MC# 990365 SILVERSEA HAS IMMEDIATELY INSPECTED, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEANED THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Silversea Cruises Ltd.
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: Silversea Cruises Ltd.
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Mediterranean Shipping Company
Date: 7/14/1999
Response: BECAUSE MEDITERRANEAN SHIPPING COMPANY IMMEDIATELY INSPECTED, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEANED THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Mediterranean Shipping Company
To: NTSB
Date: 4/12/1999
Response: Letter Mail Controlled 4/12/99 4:53:45 PM MC# 990389 MEDITERRANEAN SHIPPING COMPANY IMMEDIATELY INSPECTED, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEANED THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Mediterranean Shipping Company
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: Mediterranean Shipping Company
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Celebrity Cruises, Inc.
Date: 5/6/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT SHORTLY AFTER THE ECSTASY FIRE, BOTH ROYAL CARIBBEAN INTERNATIONAL AND CELEBRITY CRUISES, INC., DID SUCH AN INSPECTION. IN ADDITION, BOTH COMPANIES ALSO INCREASED THEIR REGULAR INSPECTION AND CLEANING OF THESE AREAS. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Celebrity Cruises, Inc.
To: NTSB
Date: 2/8/1999
Response: SHORTLY AFTER THE ECSTASY FIRE, WE LEARNED THAT BUILD UP OF LINT IN THE VENTILATION SYSTEM LEADING FROM THE LAUNDRY TO THE AFT MOORING DECK LIKELY CONTRIBUTED TO THE FIRE. BOTH ROYAL CARIBBEAN AND CELEBRITY HAD INSPECTED LAUNDRY DUCTS, PLENUMS AND EXHAUST TERMINUSES IMMEDIATELY THERAFTER TO ENSURE THAT THERE WERE NOT SIMILAR CONDITIONS WHICH WOULD CONTRIBUTE TO A FIRE. BOTH BRANDS ALSO AT THE TIME INCREASED THEIR REGULAR INSPECTION AND CLEANING OF THESE AREAS. FOLLOWING THE OCTOBER 20, 1998 SAFETY RECOMMENDATION, BOTH BRANDS AGAIN PERFORMED INSPECTIONS.

From: NTSB
To: Celebrity Cruises, Inc.
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Premier Cruise Lines
Date: 6/8/1999
Response: BECAUSE PREMIER CRUISES IMMEDIATELY INSPECTED, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Premier Cruise Lines
To: NTSB
Date: 3/23/1999
Response: Letter Mail Controlled 3/24/99 4:44:41 PM MC# 990301 PREMIER CRUISES IS IN COMPLIANCE WITH THIS RECOMMENDATION. THROUGH THE VARIOUS U.S. COAST GUARD'S INSPECTIONS CARRIED OUT ONBOARD OUR VESSELS OVER THE PAST MONTHS YOUR RECOMMENDATIONS HAVE BEEN BROUGHT TO THE ATTENTION OF THE INTERNATIONAL SHIPPING PARTNERS (OUR TECHNICAL/MARINE MANAGERS) AND MYSELF AND DEALT WITH ACCORDINGLY.

From: NTSB
To: Premier Cruise Lines
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: Premier Cruise Lines
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: Holland America Line, Inc.
To: NTSB
Date: 10/24/2001
Response: Letter Mail Controlled 02/20/2002 6:40:01 PM MC# 2020170

From: NTSB
To: Holland America Line, Inc.
Date: 7/8/1999
Response: M-98-125 ASKED THAT HOLLAND AMERICA LINE, WESTOUR AND WINDSTAR CRUISES (HOLLAND AMERICA) IMMEDIATELY INSPECT, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE. BECAUSE HOLLAND AMERICA COMPLIED WITH THIS RECOMMENDATION IN ITS ENTIRETY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Holland America Line, Inc.
To: NTSB
Date: 4/1/1999
Response: Letter Mail Controlled 4/1/99 3:33:49 PM MC# 990345 THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINISES, OF OUR SHIPS HAVE BEEN INSPECTED, FOR ANY COMBUSTIBLE MATERIAL SUCH AS LINT, AND THE SYSTEMS HAVE BEEN CLEANED AS NECESSARY TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Holland America Line, Inc.
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: Holland America Line, Inc.
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Radisson Seven Seas Cruises
Date: 1/6/1999
Response: THE BOARD UNDERSTANDS THAT RADISSON HAS PASSED THIS RECOMMENDATION TO ALL VESSELS IN ITS FLEET WITH INSTRUCTIONS TO IMMEDIATELY INSTITUTE INSPECTION AND CLEANING ROUTINES. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Radisson Seven Seas Cruises
To: NTSB
Date: 10/30/1998
Response: Letter Mail Controlled 11/4/98 4:53:52 PM MC# 981319 PER YOUR RECOMMENDATION, WE HAVE SHARED THE ABOVE NOTICE AND RECOMMENDATIONS TO BOTH THE MASTER OF EACH OF OUR VESSELS AND THE VESSELS' MANAGER, V.SHIP LEISURE GROUP AND SERVICE AND TRANSPORT. THE VESSELS HAVE BEEN INSTRUCTED TO IMMEDIATELY INSTITUTE INSPECTION AND CLEANING ROUTINES. THE TECHNICAL MANAGERS ARE ALSO REVIEWING THE VESSELS' SYSTEMS FOR POSSIBLE MODIFICATIONS DURING THE DRY DOCK PERIOD THAT IS SCHEDULED FOR 1999. MAY WE ALSO SUGGEST THAT YOU SHARE THIS INFORMATION WITH BOTH THE MAJOR SHIPYARDS IN EUROPE AND THE MANUFACTURERS OF MARINE LAUNDRY EQUIPMENT.

From: NTSB
To: Royal Caribbean Cruises Ltd.
Date: 5/6/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT SHORTLY AFTER THE ECSTASY FIRE, BOTH ROYAL CARIBBEAN INTERNATIONAL AND CELEBRITY CRUISES, INC., DID SUCH AN INSPECTION. IN ADDITION, BOTH COMPANIES ALSO INCREASED THEIR REGULAR INSPECTION AND CLEANING OF THESE AREAS. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Royal Caribbean Cruises Ltd.
To: NTSB
Date: 2/14/1999
Response: Letter Mail Controlled 2/17/99 10:30:44 AM MC# 990145

From: Royal Caribbean Cruises Ltd.
To: NTSB
Date: 2/8/1999
Response: Letter Mail Controlled 2/17/99 10:28:03 AM MC# 990144 SHORTLY AFTER THE ECSTASY FIRE, WE LEARNED THAT BUILD UP OF LINT IN THE VENTILATION SYSTEM LEADING FROM THE LAUNDRY TO THE AFT MOORING DECK LIKELY CONTRIBUTED TO THE FIRE. BOTH ROYAL CARIBBEAN AND CELEBRITY HAD INSPECTED LAUNDRY DUCTS, PLENUMS AND EXHAUST TERMINUSES IMMEDIATELY THEREAFTER TO ENSURE THAT THERE WERE NOT SIMILAR CONDITIONS WHICH WOULD CONTRIBUTE TO A FIRE. BOTH BRANDS ALSO AT THE TIME INCREASED THEIR REGULAR INSPECTION AND CLEANING OF THESE AREAS. FOLLOWING THE 10/20/98 RECOMMENDATION, BOTH BRANDS AGAIN PERFORMED INSPECTIONS.

From: NTSB
To: Royal Caribbean Cruises Ltd.
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Cunard Line Ltd.
Date: 6/14/2002
Response: On February 4, 1999, Cunard Line and Seabourn Cruise Line responded, detailing the steps they had taken to address the recommended actions on all their vessels. Accordingly, on April 14, 1999, the Safety Board classified Safety Recommendations M-98-125 and -126 "Closed--Acceptable Action." A copy of that letter is enclosed for your files.

From: Cunard Line Ltd.
To: NTSB
Date: 1/11/2002
Response: Letter Mail Controlled 02/20/2002 5:57:52 PM MC# 2020162

From: NTSB
To: Cunard Line Ltd.
Date: 4/14/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT THE COMPANIES HAVE COMPLETED A THOROUGH INSPECTION OF ITS LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS AND EXHAUST TERMINUSES, AND HAS CLEANED THE DUCTS ON ALL OF ITS VESSELS TO REDUCE THE RISK OF FIRE. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Cunard Line Ltd.
To: NTSB
Date: 2/4/1999
Response: Letter Mail Controlled 2/5/99 11:53:11 AM MC# 990093 CUNARD LINES, LTD., AND SEABOURN CRUISE LINES REPORT THAT THEY HAVE INSPECTED THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, OF OUR SHIPS HAVE BEEN INSPECTED, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE. ADDITIONALLY, CUNARD LINE HAS CONTRACTED WITH AN EXTERNAL PROFESSIONAL CONTRACTOR TO UNDERTAKE COMPREHENSIVE INSPECTION OF BOTH LAUNDRY AND GALLEY EXHAUST SYSTEMS BY VISUAL AND WHERE NECESSARY BOROSCOPTIC METHOD. INSTRUCTIONS TO INSPECTION AND CLEANING FREQUENCY CONTAINED WITHIN COMPANY SAFETY MANAGEMENT SYSTEM.

From: NTSB
To: Cunard Line Ltd.
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: First European Cruises
Date: 7/8/1999
Response: M-98-125 ASKED THAT FIRST EUROPEAN CRUISES IMMEDIATELY INSPECT, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE. BECAUSE FIRST EUROPEAN CRUISES IMMEDIATELY COMPLIED, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: First European Cruises
To: NTSB
Date: 3/29/1999
Response: THE LAUNDRY VENTILLATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINATES, OF OUR SHIPS HAVE BEEN INSPECTED, FOR OUR SHIPS HAVE BEEN INSPECTED, FOR ANY COMBUSTABLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE.

From: NTSB
To: First European Cruises
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: First European Cruises
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: American Hawaii Cruises and Delta Queen Steamboat Company
Date: 4/22/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT BOTH AMERICAN HAWAII CRUISES AND DELTA QUEEN STEAMBOAT COMPANY HAVE COMPLETED A THOROUGH INSPECTION OF THEIR VESSELS' LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS AND EXHAUST TERMINUSES; HAVE CLEANED THE DUCTS ON ALL OF THEIR VESSELS TO REDUCE THE RISK OF FIRE; AND HAVE INSTALLED NEW AND IMPROVED LINT SEPARATION EQUIPMENT ON OLDER VESSELS TO REDUCE THE AMOUNT OF LINT LEAVING THE DRYER MACHINE AREAS. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION" FOR BOTH AMERICAN HAWAII CRUISES AND DELTA QUEEN STEAMBOAT COMPANY.

From: American Hawaii Cruises and Delta Queen Steamboat Company
To: NTSB
Date: 2/4/1999
Response: Letter Mail Controlled 2/5/99 11:44:36 AM MC# 990091 AMERICAN HAWAII CRUISES & DELTA QUEEN STEAMBOAT CO. HAVE COMPLETED A THOROUGH INSPECTION OF OUR LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS AND EXHAUST TERMINUSES AND HAVE CLEANED THE DUCTS, ETC. ON ALL VESSELS UNDER OUR CONTROL TO REDUCE THE RISK OF FIRE.

From: NTSB
To: American Hawaii Cruises and Delta Queen Steamboat Company
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR A STATUS ON IMPLEMTATION OF M-98-125 AND M-98-125.

From: NTSB
To: Bergen Line, Inc.
Date: 3/17/2000
Response: THE OTHER 21 CRUISE LINES HAVE IMPLEMENTED THE RECOMMENDATIONS. BERGEN LINE IS THE ONLY CRUISE LINE THAT HAS NOT RESPONDED, DESPITE FOUR FAXES AND A JULY 16, 1999, LETTER FROM THE BOARD REQUESTING INFORMATION ON IMPLEMENTING THESE RECOMMENDATIONS. ACCORDINGLY, M-98-125 AND -126 HAVE BEEN CLASSIFIED "CLOSED--UNACCEPTABLE ACTION--NO RESPONSE RECEIVED."

From: Bergen Line, Inc.
To: NTSB
Date: 12/29/1999
Response: NO RESPONSE.

From: NTSB
To: Bergen Line, Inc.
Date: 7/16/1999
Response: THE SAFETY BOARD WOULD APPRECIATE LEARNING WHAT ACTION HAS BEEN TAKEN TO IMPLEMENT THE ABOVE SAFETY RECOMMENDATIONS (ENCLOSED) AND LOOKS FORWARD TO A PROMPT REPLY.

From: NTSB
To: Bergen Line, Inc.
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: Bergen Line, Inc.
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Renaissance Cruises, Inc.
Date: 6/8/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT RENAISSANCE HAS COMPLETED SUCH AN INSPECTION. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Renaissance Cruises, Inc.
To: NTSB
Date: 3/16/1999
Response: Letter Mail Controlled 3/17/99 3:23:28 PM MC# 990265 RENAISSANCE CRUISE LINE REPORTS THAT IT HAS INSPECTED THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, OF OUR SHIPS HAVE BEEN INSPECTED, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Renaissance Cruises, Inc.
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: Renaissance Cruises, Inc.
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Royal Olympic Cruises
Date: 4/30/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT ROYAL OLYMPIC CRUISES HAS COMPLETED A THOROUGH INSPECTION OF ITS LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS AND EXHAUST TERMINUSES, HAS CLEANED THE DUCTS ON ALL OF ITS VESSELS TO REDUCE THE RISK OF FIRE, AND HAS INSTALLED NEW AND IMPROVED LINT SEPARATION EQUIPMENT ON ITS OLDER VESSELS TO REDUCE THE AMOUNT OF LINT LEAVING THE DRYER MACHINE AREAS. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Royal Olympic Cruises
To: NTSB
Date: 2/9/1999
Response: Letter Mail Controlled 2/9/99 3:58:52 PM MC# 990126 THE LAUNDRY VENTILATION SYSTEMS OF OUR SHIPS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Royal Olympic Cruises
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Crystal Cruises
Date: 4/14/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT CRYSTAL CRUISES HAS COMPLETED SUCH AN INSPECTION AND HAS CLEANED THE DUCTS ON ALL OF ITS VESSELS. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Crystal Cruises
To: NTSB
Date: 2/3/1999
Response: Letter Mail Controlled 2/5/99 11:57:51 AM MC# 990094 CRYSTAL CRUISES COMPLETED A THOROUGH INSPECTION OF OUR LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS AND EXHAUST TERMINUSES, AND CLEANED THE DUCTS, ETC. ON ALL VESSELS UNDER OUR CONTROL TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Crystal Cruises
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Disney Cruise Line
Date: 4/22/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT THE DISNEY CRUISE LINE HAS COMPLETED SUCH AN INSPECTION. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Disney Cruise Line
To: NTSB
Date: 2/14/1999
Response: DISNEY CRUISE LINE REPORT THAT IT HAS INSPECTED THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, OF OUR SHIPS HAVE BEEN INSPECTED, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Disney Cruise Line
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Norwegian Cruise Line
Date: 7/8/1999
Response: M-98-125 ASKED THAT NORWEGIAN CRUISE LINE IMMEDIATELY INSPECT, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE. BECAUSE NORWEGIAN CRUISE LINE IMMEDIATELY INSPECTED, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEANED THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Norwegian Cruise Line
To: NTSB
Date: 4/5/1999
Response: Letter Mail Controlled 4/6/99 3:34:39 PM MC# 990366 NORWEGIAN CRUISE LINE IMMEDIATELY INSPECTED, WITHIN ITS FLEET OF SHIPS, THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUST TERMINUSES, FOR ANY COMBUSTIBLE MATERIAL, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Norwegian Cruise Line
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: Norwegian Cruise Line
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.

From: NTSB
To: Costa Cruise Lines
Date: 4/30/1999
Response: THE SAFETY BOARD IS PLEASED TO LEARN THAT COSTA CRUISE LINES HAS COMPLETED SUCH AN INSPECTION AND HAS INSTALLED INSPECTION HATCHES TO FACILITATE FOLLOW-ON INSPECTIONS. ACCORDINGLY, M-98-125 HAS BEEN CLASSIFIED "CLOSED--ACCEPTABLE ACTION."

From: Costa Cruise Lines
To: NTSB
Date: 3/23/1999
Response: PRESTIGE CRUISE MGT. REPORTS FOR COSTA CRUISE LINE THAT IT HAS IMMEDIATELY INSPECTED, WITHIN YOUR FLEET OF SHIPS THE LAUNDRY VENTILATION SYSTEMS, INCLUDING DUCTS, PLENUMS, AND EXHAUT TERMINEUSES, FOR ANY COMBUSTIBLE MATERIALS, SUCH AS LINT, AND CLEAN THE SYSTEMS, AS NECESSARY, TO REDUCE THE RISK OF FIRE.

From: NTSB
To: Costa Cruise Lines
Date: 3/15/1999
Response: THE SAFETY BOARD AGAIN ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND -126.

From: NTSB
To: Costa Cruise Lines
Date: 2/2/1999
Response: THE SAFETY BOARD ASKED BY FAX FOR STATUS ON IMPLEMENTATION OF M-98-125 AND M-98-126.