Safety Recommendation Report: Natural Gas Distribution System Project Development and Review (Urgent)

Executive Summary

​Ongoing Investigation

On September 13, 2018, about 4:00 p.m. eastern daylight time, a series of explosions and fires occurred after high-pressure natural gas was released into a low-pressure gas distribution system in the northeast region of the Merrimack Valley, Massachusetts. The distribution system was owned and operated by Columbia Gas of Massachusetts (Columbia Gas), a subsidiary of NiSource, Inc. The system overpressure damaged 131 structures, including at least 5 homes that were destroyed in the city of Lawrence and the towns of Andover and North Andover. Most of the damage was a result of structure fires ignited by gas-fueled appliances. Several structures were destroyed by natural gas explosions. One person was killed and at least 21 individuals, including 2 firefighters, were transported to the hospital. Seven other firefighters received minor injuries.

Note: This report was reissued on December 6, 2018 with a correction to page 2.


Probable Cause

​Recommendations

As a result of this report, the National Transportation Safety Board makes the following safety recommendations:

To the Commonwealth of Massachusetts:

Eliminate the professional engineer licensure exemption for public utility work and require a professional engineer’s seal on public utility engineering drawings. (P-18-005)

To NiSource, Inc.:

Revise the engineering plan and constructability review process across all of your subsidiaries to ensure that all applicable departments review construction documents for accuracy, completeness, and correctness, and that the documents or plans be sealed by a professional engineer prior to commencing work. (P-18-006) (Urgent)

Review and ensure that all records and documentation of your natural gas systems are traceable, reliable, and complete. (P-18-007) (Urgent)

Apply management of change process to all changes to adequately identify system threats that could result in a common mode failure. (P-18-008) (Urgent)

Develop and implement control procedures during modifications to gas mains to mitigate the risks identified during management of change operations. Gas main pressures should be continually monitored during these modifications and assets should be placed at critical locations to immediately shut down the system if abnormal operations are detected. (P-18-009) (Urgent)


Accident Location: Lawrence , MA USA Merrimack Valley
Accident Date: 9/13/2018
Accident ID: PLD18MR003

Date Adopted: 11/14/2018
NTSB Number: PSR1802
NTIS Number: